Siemens S7-300 SM332 PLC 6ES7 332-5HD01-0AB0 analog output sm 332- 4 AO in BD.
Technical data:
| value DC | 24 V DC |
| load voltage L+ maximum. | 240 mA |
| backplane bus 5 V DC, maxium. | 60 mA |
| loss Power, type. | 3 W |
| analog outputs number | 4 |
| Voltage output type | Yes |
| Voltage output, maximum. | 25 mA |
| Current output, maximum. | 18 V no-load (voltage) |
| 0 to 10 Voltage | Yes |
| 1 to 5 Voltage | Yes |
| -10 to +10 Voltage | Yes |
| 0 to 20 mA | Yes |
| -20 to +20 mA | Yes |
| 4 to 20 mA | Yes |
| minimum voltage outputs | 1 kW |
| maximum voltage outputs | 1 µF (capacitive load) |
| maximum current outputs | 500 W |
| outputs current, maximum. | 10 mH (inductive load) |
| maximum Cable length | 200 m shielded |
| Maximum Resolution over the range, Siemens S7-300 SM332 | 12 bit ; +/-10 V, +/-20 mA, 4 to 20 mA, 1 to 5 V: 11 bits + sign; 0 to 10 V, 0 to 20 mA: 12 bits (bit including sign) |
Specification
| Conversion time | 0.8 ms/channel |
| Resistive load | 0.2 ms |
| Capacitive load | 3.3 ms |
| Inductive load | 0.5 ms (1 mH) and 3.3 ms (10 mH) |
| Relative to output area Voltage | (+/-) 0,5 % |
| Relative to output area Current | (+/-) 0,6 % |
| Voltage output relative area | (+/-) 0,4 % |
| Current output relative area | (+/-) 0,5 % |
| Substitute values connectable | Yes; Parameterizable |
| Diagnostic alarm | Yes; Parameterizable |
| Diagnostic information readable | Yes |
| Diagnostics | Yes |
| Group error SF (red) | Yes |
| Channels and backplane bus (compare) | Yes |
| Isolation checked with | 500 V DC |
| Required front connector | 20-pin |